CA1910065_DST_804 DISINFECTION BYPRODUCTS-202311 2943 BROMODICHLOROMETHANE 8.050 1.000 UG/L 1 08-15-2023 3 2023/11 DUE NOW
CA1910065_DST_804 DISINFECTION BYPRODUCTS-202311 2942 BROMOFORM 1.950 1.000 UG/L 1 08-15-2023 3 2023/11 DUE NOW
CA1910065_DST_804 DISINFECTION BYPRODUCTS-202311 2941 CHLOROFORM 10.000 1.000 UG/L 1 08-15-2023 3 2023/11 DUE NOW
CA1910065_DST_804 DISINFECTION BYPRODUCTS-202211 2454 DIBROMOACETIC ACID 2.300 1.000 UG/L 1 08-16-2022 3 2022/11 DUE NOW
CA1910065_DST_804 DISINFECTION BYPRODUCTS-202311 2944 DIBROMOCHLOROMETHANE 7.620 1.000 UG/L 1 08-15-2023 3 2023/11 DUE NOW
CA1910065_DST_804 DISINFECTION BYPRODUCTS-202211 2451 DICHLOROACETIC ACID 8.500 1.000 UG/L 1 08-16-2022 3 2022/11 DUE NOW
CA1910065_DST_804 DISINFECTION BYPRODUCTS-202211 2456 TOTAL HALOACETIC ACIDS (HAA5) 14.000 6.000 UG/L 60 08-16-2022 3 2022/11 DUE NOW
CA1910065_DST_804 DISINFECTION BYPRODUCTS-202211 2453 MONOBROMOACETIC ACID < 1.000 UG/L 1 08-16-2022 3 2022/11 DUE NOW
CA1910065_DST_804 DISINFECTION BYPRODUCTS-202211 2450 MONOCHLOROACETIC ACID < 2.000 UG/L 2 08-16-2022 3 2022/11 DUE NOW
CA1910065_DST_804 DISINFECTION BYPRODUCTS-202311 2950 TTHM 27.700 4.000 UG/L 80 08-15-2023 3 2023/11 DUE NOW
CA1910065_DST_804 DISINFECTION BYPRODUCTS-202211 2452 TRICHLOROACETIC ACID 3.300 1.000 UG/L 1 08-16-2022 3 2022/11 DUE NOW
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

*Please refer to the Stage 2 DBP Monitoring Plan Approval Letter for full sample point names.
RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.